| Breaking Capacity | Material | Operating Temperature |
| 6KAat 240V AC(1A-13A) | Fuse body -- Ceramic tube End cap -- Nickel-plated brass | -40℃~+125℃ |
| Testing current | Blow Time | |
| Min | Max | |
| 100% | 1000 hours | - |
| 160% | 30min | - |
| 190% | - | 30min |
● Pending
○ Approvals
| Current Rating | Voltage Rating 264V max. | Norminal Melting I²T(A²sec) For Reference | Approvals | |
![]() | ![]() | |||
| 1A | 240V | 1.44 | ● | ● |
| 2A | 240V | 12.81 | ● | ● |
| 3A | 240V | 36.60 | ● | ● |
| 5A | 240V | 82.08 | ● | ● |
| 7A | 240V | 179.02 | ● | ● |
| 10A | 240V | 443.10 | ● | ● |
| 13A | 240V | 714.49 | ● | ● |